Context plus XFP single loop 16 zone addressable fire alarm panel offers high performance

Ideal for use in small stand-alone applications or in larger applications due to its ability to sit on network of up to 8 XFP master panels

LPCB certified to EN54 parts 2 & 4, it is supplied in an attractive flush or surface mountable plastic enclosure, offers combined keypad or keyswitch entry to Access Levels 2 and 3 and is compatible with Apollo’s XP95/Discovery protocol.

 

Technical specifications

Approvals/certifications  

Certified to EN54-2 & 4 by the LPCB.

Protocol/compatibility     

Apollo XP95/Discovery.

Mains supply      

230V 50/60Hz.

Mains rated current          

350mA maximum.

Internal power supply       

27Vdc nominal.

Total output current limited to       

1.4A @ 230Vac (Imax.A 210mA; Imin. 40mA).

Quiescent current             

50mA (loop unloaded).

Max battery size and type

2 x 12V 3.2Ah VRLA connected in series.

No. of loop drivers            

1.

Max. loop output current 

500mA (25V min; 34V max).

Max. loop length

1KM.

Max. addressable devices per loop

126.

No. of conventional sounder circuits            

2 (Max. length per circuit is 500m).

EOL resistor value             

6800Ω 5% Tol. 0/25W (blue, grey, red, gold).

Max. sounder output current         

400mA.

Auxiliary relays   

3 x Programmable Relays (programmable from C&Es). 1 x Fault Relay (active when no faults are present). Volt free single pole changeover. Max. switch current 1A; Max. switch voltage 30Vdc.

Other outputs     

24V Aux. Power (19.5V min, 28V max). Protected by a resettable fuse. Max. current 100mA.

Auxiliary inputs  

2 x Programmable Inputs (programmable from C&Es). Connect to 0V to trigger, Max. input voltage 27V (non-latching).

PC connection     

PC connection via RS232 molex connector (supplied in XFP507 upload/download software kit); No printer connection available.

Indicators            

2 line x 40 character backlit display; 16 Zonal LEDs, General Fire; Energised; Pre-Alarm; Remote Output Activated; Remote Output Disabled; Accessed; Disablement; Test; Silenced; General Fault; Syst

Connections        

Fixed, largest acceptable conductor size 1mm2.

Expansion connections     

2-wire RS485 non-redundant network/repeater connection available via optional XFP761 network card. Max. 8 mains per network or 8 repeaters per non-networked main. Limit 1KM (main panel network) or

Product dimensions (mm)

380 W x 235 H x D 96mm (hole required for flush mounting = 367 W x 220 H x 75 D mm. No bezel required).

Construction & finish        

Plastic lid and base; RAL7035 textured

IP Rating

IP30.

Weight  

1.8kg (without batteries).

Operating conditions/temperature

-5ºC to +40ºC. Max relative humidity: 95%.