Context plus XFP two loop 32 zone addressable fire alarm panel offers high performance and Ideal for use in small stand-alone applications or in larger applications due to its ability to sit on network of up to 8 XFP master panels, it is one of Europe’s best-selling addressable fire panels.
LPCB certified to EN54 parts 2 & 4, it is supplied in durable metal enclosure, offers combined keypad or keyswitch entry to Access Levels 2 and 3 and is compatible with Apollo’s XP95/Discovery protocol.
Packed full of engineering features – please refer to the feature list below – the XFP502/X is also fully compatible with C-TEC’s Hush Button fire alarm solution and its new range of EN54 certified addressable sounders and VADs.
Technical Specifications
Approvals/certifications
Certified to EN54-2 & 4 by the LPCB.
Protocol/compatibility
Apollo XP95/Discovery.
Mains supply
230V 50/60Hz.
Mains rated current
680mA maximum.
Internal power supply
27Vdc nominal.
Total output current limited to
3A @ 230Vac (Imax.A 270mA; Imin. 70mA).
Quiescent current
100mA (2 loops unloaded).
Max battery size and type
2 x 12V 7Ah VRLA connected in series.
No. of loop drivers
2.
Max. loop output current
500mA (25V min; 34V max).
Max. loop length
1KM.
Max. addressable devices per loop
126.
No. of conventional sounder circuits
2 (Max. length per circuit is 500m).
EOL resistor value
6800Ω 5% Tol. 0/25W (blue, grey, red, gold).
Max. sounder output current
400mA.
Auxiliary relays
3 x Programmable Relays (programmable from C&Es). 1 x Fault Relay (active when no faults are present). Volt free single pole changeover. Max. switch current 1A; Max. switch voltage 30Vdc.
Other outputs
24V Aux. Power (19.5V min, 28V max). Protected by a resettable fuse. Max. current 100mA.
Auxiliary inputs
2 x Programmable Inputs (programmable from C&Es). Connect to 0V to trigger, Max. input voltage 27V (non-latching).
PC connection
PC connection via RS232 molex connector (supplied in XFP507 upload/download software kit); No printer connection available.
Indicators
2 line x 40 character backlit display; 32 Zonal LEDs, General Fire; Energised; Pre-Alarm; Remote Output Activated; Remote Output Disabled; Accessed; Disablement; Test; Silenced; General Fault; Syst
Connections
Fixed, largest acceptable conductor size 1mm2.
Expansion connections
2-wire RS485 network/repeater connection available via optional AFP711 network card. Max. 8 mains per network or 8 repeaters per non-networked main. Limit 1KM (main panel network) or 500M (repeater
Product dimensions (mm)
410 W x 250 H x 80 D mm (base); 439 W x 274 H x 7 D mm (lid).
Construction & finish
Metal.
IP Rating
IP30.
Weight
4.5kg (without batteries).
Operating conditions/temperature
-5ºC to +40ºC. Max relative humidity: 95%.
.